1/03 UDC 6300 Process Controller Product Manual 57
3.16 Loop 2 Control Parameters Set Up Group, Continued
Function prompts,
continued
Table 3-13 lists all the function prompts in the “CONTROL2” Set Up
group.
Table 3-13 Control2 Group Function Prompts, continued
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
ACTION
Control Output Direction DIRECT
REVERSE
REVERSE
OUT RATE
Output Change Rate ENABLE
DISABLE
DISABL
PCT/MIN UP
Output Rate Up Value 0 to 9999% / minute 0
PCT/MIN DN
Output Rate Down Value 0 to 9999% / minute 0
OUTHILIM
High Output Limit –5.0 to 105.0% of output 100.0
OUTLOLIM
Low Output Limit –5.0 to 105.0% of output 0
I HI LIM
High Reset Limit Within the range of the output
limits
100.0
I LO LIM
Low Reset Limit Within the range of the output
limits
0.0
DROPOFF
Controller Dropoff Value –5.0 to 105.0% of output 0.0
DEADBAND
Output Relay Deadband Duplex: only
–5.0 to 25.0%
All others
0.0 to 25.0%
1.0
FAILMODE
Failsafe Mode NON LATCH
LATCHING
NON LATCH
FAILSAFE
Failsafe Output Value Set within the range of the output
limits. 0 to 100%
0.0