190 UDC 6300 Process Controller Product Manual 1/03
5.17 Digital Outputs, Continued
Configuration Options
- Digital Outputs 1 and
2
Digital Outputs 1 and 2 can also be configured to operate as an Output for
a Logic gate:
• GATE 1 OUT, GATE 2 OUT, GATE 3 OUT, GATE 4 OUT, or
GATE 5 OUT prompt, under Set Up Group “Advanced Math”,
configured for DIG OUT 1 or DIG OUT 2.
Configuration options
- Digital Outputs 3 and
4
Digital Outputs 3 and 4 have several different configuration options from
which to choose:
DIGITAL OUTPUT 3
• DIG IN 1 (Digital Input 1) or DIG IN2 (Digital Input 2) prompt,
under Set Up Group “Options”, configured for OUT 3 ON.
• A3S1 TYPE (Alarm 3, Setpoint 1) or A3S2 TYPE (Alarm 3,
Setpoint 2) prompt, under Set UP Group “Alarms”, configured
for any selection except “NONE”.
• OUT ALG (Output Algorithm) prompt, under Set Up Group
“Output Algorithm”, configured for TIME, TIME DPLX,
CUR TIME, or TIME CUR.
• GATE 1 OUT, GATE 2 OUT, GATE 3 OUT, GATE 4 OUT, or
GATE 5 OUT prompt, under Set Up Group “Advanced Math”,
configured for DIG OUT 3
DIGITAL OUTPUT 4
• DIG IN 1 (Digital Input 1) or DIG IN2 (Digital Input 2) prompt,
under Set Up Group “Options”, configured for OUT 4 ON.
• A4S1 TYPE (Alarm 4, Setpoint 1) or A4S2 TYPE (Alarm 4,
Setpoint 2) prompt, under Set UP Group “Alarms”, configured
for any selection except “NONE”.
• OUT ALG (Output Algorithm) prompt, under Set Up Group
“Output Algorithm”, configured for TIME DPLX.
• OUT2ALG (Output Algorithm 2) prompt, under Set Up Group
“Output Algorithm”, configured for TIME, CUR TIME, or
TIME CUR.
• GATE 1 OUT, GATE 2 OUT, GATE 3 OUT, GATE 4 OUT, or
GATE 5 OUT prompt, under Set Up Group “Advanced Math”,
configured for DIG OUT 4
Continued on next page