1/03 UDC 6300 Process Controller Product Manual 15
2.5 Wiring
Taking electrical
noise precautions
Electrical noise is composed of unabated electrical signals which produce
undesirable effects in measurements and control circuits.
Digital equipment is especially sensitive to the effects of electrical noise.
Your controller has built-in circuits to reduce the effect of electrical noise
from various sources. If there is a need to further reduce these effects:
Separate External Wiring - separate connecting wires into bundles (see
Table 2-4) and route the individual bundles through separate conduits or
metal trays.
Use Suppression Devices - for additional noise protection, you may want
to add suppression devices at the external source. Appropriate suppression
devices are commercially available.
NOTE
For additional noise information, refer to Appendix B.
Permissible wire
bundling
Table 2-4 shows which wire functions should be bundled together.
Table 2-4 Permissible Wiring Bundling
Bundle No. Wire Functions
1
• Line power wiring
• Earth ground wiring
• Control relay output wiring
• Line voltage alarm wiring
2 Analog signal wire, such as:
• Input signal wire (thermocouple, 4 to 20 mA, etc.)
• 4-20mA output signal wiring
• Slidewire feedback circuit wiring
• Digital input signals
• Communications
3 • Low voltage alarm relay output wiring
• Low voltage wiring to solid state type control circuits