238 UDC 6300 Process Controller Product Manual 1/03
6.12 Restoring Factory Calibration, Continued
Procedure, continued
Table 6-10 Restoring Factory Calibration, continued
Step Operation Press Action/Result
INPUT 5
4
Enter
“INPUT 5”
Setup Group
SET
UP
Until you see:
Upper Display
Lower Display
SET UP
INPUT 5
FUNC
L1/L2
Until you see:
Upper Display
Lower Display
IN5 TYPE
Current Selection
or
to change the current selection to
another selection.
FUNC
L1/L2
Until the lower display rolls through the
rest of the functions and returns to
Upper Display
Lower Display
IN5 TYPE
Current Selection
or
Until you change the input selection in
the upper display back to the proper
selection. You will see:
Upper Display
Lower Display
Original input
selection that
matches your
type of sensor.
IN5 TYPE
5
Return to
normal
operating
mode
LOWR
DISP
To return to Normal operating mode.
The factory calibration will be restored. If
the problem is not corrected, contact the
Honeywell Technical Assistance Center
1-800-423-9883 USA
1-800-461-0013 Canada
Continued on next page