1/03 UDC 6300 Process Controller Product Manual 123
4.13 Options Set Up Group, Continued
Table 4-12 Option Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
DIG IN 1
continued
TRACK 2 OUTPUT2 TRACKS INPUT 4 — Contact closure
allows OUT 2 to track Input 4.
TO OUT 2 OUT 2 OVERRIDES OUTPUT 1 — Allows OUT 2 to
override OUT 1.
MAN SAFE MANUAL FAILSAFE – Unit goes to Manual Mode,
output goes to the Failsafe value.
PULSE DOWN SETPOINT DOWN — Contact closure selects
downward direction of setpoint when Pulse Input is
used as a setpoint adjustment. Open Contact
selects Upward direction.
OUT 3 ON OUTPUT 3 ON — Contact closure energizes Output
3. This selection is overridden by Time
Proportioning Output selections and Alarm 3.
OUT 4 ON OUTPUT 4 ON — Contact closure energizes Output
4. This selection is overridden by Time
Proportioning Output selections and Alarm 4.
INHIBIT 1 INHIBITS INTEGRAL ACTION — Contact Closure
inhibits integral action on PID-A or PID-B algorithms.
TO RSP TO REMOTE SETPOINT — Contact closure selects
the Remote Setpoint.
DSP L1/L2 LOOP DISPLAY — Contact closure displays loop
not currently being displayed. Opening contact
returns to original loop display.
RESET FB INTEGRAL RESET OVERRIDE - Contact closure
allows Input 3 to override the Integral Reset
Calculation.
Note: Input 3 Ratio and Bias settings are ignored
and should be set to 1.00 and 0.00 to make the
value consistent with the front display readout. The
value used is in percent of the range.
ToA/M STA TO AUTO MANUAL STATION - When the switch is
closed, the loop performs as follows:
PV = In2
Action = Direct
Control Algorithm = PD+MR
PIDSET = 2
SP = LSP2
TO PURGE TO PURGE - When the switch is closed, the loop is
forced to Manual mode with the Output value set to
the High Output Limit. The configuration of the
Latching function determines whether the action is
momentary or latching.
LOW FIRE TO LOW FIRE - When the switch is closed, the loop
is forced to Manual mode with the Output value set
to the Low Output Limit. The configuration of the
Latching function determines whether the action is
momentary or latching.
ToTUNE ToTUNE - contact closure starts the tuning process.
Table 4-12 continued on next page