1/03 UDC 6300 Process Controller Product Manual 119
4.12 Control2 Parameters Set Up Group, Continued
Table 4-11 Control2 Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
PCT/MIN UP
0 to 9999%/minute
OUTPUT RATE UP VALUE - This selection limits
the rate at which the output can change upward.
Enter a value in percent/minute. Appears only if
“OUT RATE” is enabled. “0” means no output rate
applied.
PCT/MIN DN
0 to 9999%/minute
OUTPUT RATE DOWN VALUE - This selection
limits the rate at which the output can change
downward. Enter a value in percent/minute. Appears
only if “OUT RATE” is enabled. “0” means no output
rate.
OUT HI LIM
–5.0 to 105.0% of output
HIGH OUTPUT LIMIT — This is the highest value of
output beyond which you do not want the controller
automatic output to exceed.
Use 0 to 100% for digital output type.
Use 5 to 105% for current output.
OUT LO LIM
–5.0 to 105.0% of output
LOW OUTPUT LIMIT — This is the lowest value of
output below which you do not want the controller
automatic output to exceed.
Use 0 to 100% for digital output type.
Use 5 to 105% for current output.
I HI LIM
Within the range of the
output limits
HIGH RESET LIMIT - this is the highest value of
output beyond which you want no reset to occur.
I LOLIM
Within the range of the
output limits
LOW RESET LIMIT - this is the lowest value of
output beyond which you want no reset to occur.
DROPOFF
–5 to 105.0% of output
CONTROLLER DROPOFF VALUE — Output value
that below which the controller output will dropoff to
the low output limit value set in prompt "OUT
LOLIM."
DEADBAND
–5.0 to 25.0%
0 to 25.0%
DEADBAND is an adjustable gap between the
operating ranges of output 1 and output 2 in which
neither output operates (positive value) or both
outputs operate (negative value).
Time Duplex, Cur Duplex, Cur Time, Time Cur
On-Off Duplex
FAIL MODE
NON LATCH
LATCHING
FAILSAFE MODE
NON LATCH - When the controller has gone to
failsafe and the problem is corrected, the controller
will go to automatic mode on power up at the
setpoint that was being used.
LATCHING - When the controller has gone to
failsafe and the problem is corrected, the controller
will stay in manual mode.
FAILSAFE
0 to 100%
FAILSAFE OUTPUT VALUE — The value used
here will also be the output level when you have
Communications SHED or when NO BURNOUT is
configured and input 1 fails.