136 UDC 6300 Process Controller Product Manual 1/03
4.15 Alarms Set Up Group, Continued
Table 4-14 Alarms Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
A3S1 H L*
H I
LO
ALARM 3 SETPOINT 1 STATE — Select whether
you want the alarm type chosen in Prompt
"A3S1TYPE" to alarm HIGH or LOW.
HI ALARM
LO ALARM
A3S2 H L*
H I
LO
ALARM 3 SETPOINT 2 STATE — Select whether
you want the alarm type chosen in Prompt
"A3S2TYPE" to alarm HIGH or LOW.
HI ALARM
LO ALARM
A4S1 H L*
H I
LO
ALARM 4 SETPOINT 1 STATE — Select whether
you want the alarm type chosen in Prompt
"A4S1TYPE" to alarm .
HI ALARM
LO ALARM
A4S2 H L*
H I
LO
ALARM 4SET POINT 2 STATE — Select whether
you want the alarm type chosen in Prompt
"A4S2TYPE" to alarm HIGH or LOW.
HI ALARM
LO ALARM
AL HYST
0.0 to 5.0% of span or full
output as appropriate
ALARM HYSTERESIS — A single adjustable
hysteresis is provided on alarms such that when the
alarm is OFF it activates at exactly the alarm
setpoint; when the alarm is ON, it will not deactivate
until the variable is 0.0% to 5.0% away from the
alarm setpoint.
Configure the hysteresis of the alarms based on
INPUT signals as a % of input range span.
Configure the hysteresis of the alarm based on
OUTPUT signals as a % of the full scale output
range.
ALM ACTN
ENERGIZE
DE ENERGZ
ALARM RELAY COIL ACTION - The alarm action
is configurable for normally de-energized (Reverse)
operation.
ENERGIZE - Digital Output energized on alarm.
DE ENERGZ - Digital Output de-energized on alarm.
• AxSxHL is not available for AxSx TYPE: NONE, SHED, MANUAL, MANUAL2, REMSP, REMSP2, FAILSAFE,
FAILSAFE2.
Continued on next page