1/03 UDC 6300 Process Controller Product Manual 211
5.22 Three Position Step Control, Continued
Setting the motor
travel time, continued
Table 5-44 Procedure for Setting the 3PSTEP Motor time, continued
Step Operation Press Action
3
Enter the Motor
Travel Time
FUNC
L1/L2
Until you see:
Upper Display
Lower Display
MTR TIME
(Motor Time
in seconds)
or
To select the Motor Travel Time.
Range of setting: 5 to 255 seconds
Displaying the motor
position
Table 5-45 lists the procedure for displaying the motor position.
Table 5-45 Procedure for Displaying the 3PSTEP Motor Position
Step Operation Press Action
1
Access the
displays
LOWR
DISP
Until you see:
Lower Display
Upper Display
The PV value
OUT and the estimated 3PStep
motor position in percent.
Power up output
When the controller powers up after a power outage, the position of the
motor will correspond to whatever was configured at set up group prompt
“CONTROL”, function prompt “PWR MODE”, selection MANUAL,
AorM SP, or AorM LSP. Refer to Subsection 4.11, Table 4-10 for
definition of each selection.
If Burnout = NONE is configured for the PV Input, the FAILSAFE output
value in the “CONTROL” group must be configured for 0% or 100%.