186 UDC 6300 Process Controller Product Manual 1/03
5.15 Input Math Algorithms, Continued
Totalizer function
A Flow Totalizer is available as part of the Math Algorithm option. This
calculates and displays the total flow volume being measured by input 1.
Alternatively, it can be applied to either Input Algorithm 1 or Input
Algorithm 2 to totalize the compensated flow rate being calculated by the
algorithm.
The totalizer displays the current totalized flow value (up to eight digits
maximum). Seven scaling factors are available (from 1 to 1 million). The
desired scaling factor is applied to the calculated value to extend the
maximum total flow range that can be displayed.
Five integration rates are available to match the totalizer rate to the rate
of flow being measured. The rate are:
Engineering Units (EU) per second
EU per minute
EU per hour
EU per day
Millions of units per day
The Totalizer value is stored in non-volatile memory once every eight
hours. If power is lost while the totalizer is in operation, the current value
of the totalizer will be lost. When power is restored, the Totalizer will
start operation for the last value stored in non-volatile memory. The “Σ
(Sigma)” display will blink to indicate this condition. Reset the Totalizer.
The Totalizer can be reset from the keyboard whenever desired or by
configuring a Comparator Logic Gate.
The Totalizer should always be reset to initialize the counters whenever it
is enabled, otherwise, the “Σ (Sigma)” display will blink
Refer to Section 3 - Configuration, Set Up group ALGORTHM”, function
prompt “TOTALIZER” to select an application and the function prompts
that follow “TOTALIZER” to enter your scale factor and rate of
integration.