1/03 UDC 6300 Process Controller Product Manual 105
4.8 Output Algorithm Data Set Up Group, Continued
Table 4-7 Output Algorithm Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
4-20 RNG
CURRENT DUPLEX RANGE ALGORITHM — Used
with Output Algorithm selections "CUR-DPLX,"
"CUR-TIME", or "TIME-CUR."
50 PCT
CURRENT DUPLEX RANGE (SPLIT) For "CUR
DPLX" this enables the normal control current output
to provide iheat control and the 2nd current output to
provide cool control. To enable this, "CUR OUT 2"
in the “Options” Set up group must be:
•Selected for OUTPUT
• 2ND current output is scaled as desired for
0-50% controller output (4mA set to 50;
20mA set to 0)
• Deadband for this configuration only applies to
the Current output The second current output
must have the Deadband scaled in.
For example:
If a 2% Deadband is desired, then enter a “2.0” for the
“Deadband” selection in the Control group. This will apply
Deadband to the Current Output. In the “Opyions” group,
set the 2nd Current Output “4mA VAL” selection to “49.0”
and the “20mA” selection to “0”.
100PCT
CURRENT DUPLEX RANGE (FULL) enables the
normal control current output to provide duplex
control over 0 - 100% of the controller output by
providing cool control over 4–12 mA and Heat
control over 12–20 mA. The second current output is
not required for this type of duplex operation.
OUTALG 2
NONE
TIME
CURRENT
CUR DPLX
CUR TIME
TIME CUR
The OUTPUT ALGORITHM lets you select the type
of output you want for the second control loop
See "OUTALG" for definitions.
NONE - No selection
TIME - Uses Digital Output 4
CURRENT - Uses second current output
CUR DPLX- Uses second current output
CUR TIME - Digital Output 4 = Heat, Second
Current Output = Cool
TIME CUR - Digital Output 4 = Cool, Second
Current Output = Heat
DO STATE
3OFF 4OFF
3ON 4ON
3OFF 4ON
3ON 4 OFF
DIGITAL OUTPUT STATUS AT 0% OUTPUT -
allows the following selections:
3OFF 4OFF Output 3 de-energized
Output 4 de-energized
3ON 4ON Output 3 energized
Output 4 energized
3OFF 4ON Output 3 de-energized
Output 4 energized
3ON 4 OFF Output 3 energized
Output 4 de-energized
ATTENTION
For units not configured for Time
Duplex, Output 4 is always de-energized.