1/03 UDC 6300 Process Controller Product Manual 137
4.15 Alarms Set Up Group, Continued
Table 4-14 Alarms Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
ALM OUT 1
NON LATCH
LATCHING
LATCHING ALARM FOR OUTPUT 1 - each alarm
output can be configured to be "Latching" or "Non-
latching".
Table 4-15 shows you the operation of the Digital
Outputs, Annunciators, and Bargraphs when you
select "Latching" or "Non-latching" alarms.
ALM OUT 2
NON LATCH
LATCHING
LATCHING ALARM FOR OUTPUT 2 - each alarm
output can be configured to be "Latching" or "Non-
latching".
ALM OUT 3
NON LATCH
LATCHING
LATCHING ALARM FOR OUTPUT 3 - each alarm
output can be configured to be "Latching" or "Non-
latching".
ALM OUT 4
NON LATCH
LATCHING
LATCHING ALARM FOR OUTPUT 4 - each alarm
output can be configured to be "Latching" or "Non-
latching".
Table 4-15 Latching and Non-latching Alarm Configuration
Alarm
Configuratio
n
Alarm
Condition
Alarm ACK
Key
Digital Outputs Annunciator
s
***
Bargraphs
Pressed EN* DEN**
STILL
EXISTS
NO ON OFF FLASHING FLASHING
Non
YES ON OFF ON NORMAL
Latching
ENDED NO OFF ON OFF NORMAL
YES OFF ON OFF NORMAL
STILL
EXISTS
NO ON OFF FLASHING FLASHING
Latching****
YES ON OFF ON NORMAL
ENDED NO ON OFF FLASHING FLASHING
YES OFF ON OFF NORMAL
* "EN" is the "Digital Outputs Energized on Alarm" configuration
** "DEN" is the "Digital Outputs De-energized on Alarm" configuration
*** Only the Annunciator associated with the alarm will flash.
**** For CE conformity, Performance Criterion A, select “NON-LATCHING”.